1、毕业设计(论文)题目名称:北京某办公楼中央空调系统设计学院名称:能源与环境学院班 级:学 号:学生姓名:指导教师: 年 月 日-131-论文编号:北京某办公楼中央空调系统设计The central air conditioning system design of office building 学院名称:能源与环境学院班 级:学 号:学生姓名:指导教师: 年 月 日摘 要 本工程为北京某办公楼中央空调系统,拟为之设计合理的中央空调系统为室内人员提供舒适的工作环境。建筑共五层,总面积为4365,层高4.0m。设计内容包括:空调冷负荷计算;空调系统划分与系统方案的确定;风系统的设计与计算;室内送
2、风方式与气流组织形式的确定;风管系统保温层的设计;消声防震设计等内容。空调设计中,大空间采用全空气一次回风的空气处理方案,从节能的角度考虑,采用露点送风。空气处理机组设在每层的空调机房内,新回风经集中处理后送入各空调房间。气流组织采用上送上回的气流组织形式,送风口选用方形散流器,回风口采用单层百叶回风口。其余空调房间因面积较小,采用风机盘管加新风系统,将室外新风处理到低于室内空气焓值的状态,承担室内全部湿负荷和部分冷负荷。新风由设置在走廊内的吊顶新风机组处理后送入各房间。风机盘管送风选用侧送式,安装形式为卧式暗装。空调用制冷机房设在地下室,选用一台螺杆式冷水机组。夏天使用冷水机组提供的7/12
3、的冷水。水管路采用两管制。冷却塔置于屋顶,配一台。关键词:办公楼,全空气系统,风机盘管系统,性能比较AbstractThis works for a between production in beijing central air-conditioning system, so as to create a comfortable work environment for the stuff. Construction of 5 layer, the total area of 4365 , the layer is 4.0 m. It contains: cooling load calc
4、ulation; air conditioning system division and system solutions to determine the; the wind system design and calculation; indoor air distribution mode and the airflow organization form of sure; duct system design of insulation layer; noise and vibration control, etc. In air conditioning design, 1F us
5、e the entire air time to return to the wind the air processing plan. From energy conservation angle consideration, Uses the dew point blast. The air processing unit is located in each level in the air conditioning engine room, New、returns to the wind to send in various air conditioned room after cen
6、tralism processing, The air current organization form used on delivers the other day, Delivers the gusty area to select square shape drifting. Returns to the gusty area to use the monolayer drifting to return to the gusty area.Other air conditioned rooms because the area is smaller, Uses the air blo
7、wer plate tube to add the new atmosphere system, Outside the new atmosphere will process to is lower than in the room the air enthalpy value condition, Undertakes in the room completely the wet load and the partial cold loads, The new atmosphere by establishes the suspended ceiling new atmosphere un